Inspection Criteria
(1) No holes or breaks in door or frame.
(2) Glazing and glass kit/glass beads are intact and securely fastened.
(3) Door, frame, and hardware are in proper working order.
(4) No missing or broken parts.
(5) Door clearances are within allowable limits.
(6) Door closer/spring hinges are operational and door is self-closing.
(7) Coordinator ensures that door leaves close in proper sequence (pairs only).
(8) Door is self-latching in the closed position.
(9) Opening is not equipped with auxiliary hardware items which interfere with operation.
(10) No field modifications have been performed that void the label.
(11) Gasketing and edge seals, where required, are present, continuous, and of the proper type for a fire door.